For a chiller, choose the glycol percentage whose freezing point is about 10 °C below the leaving fluid temperature, so that it stays 5 to 8 °C below the evaporating temperature. As a guide, 30 % ethylene glycol freezes at about −15 °C and 40 % at about −24 °C; propylene glycol needs a few percent more for the same protection. Use only inhibited industrial glycol.
Ethylene glycol freezing point chart
| Ethylene glycol (% by volume) | Approximate freezing point | Typical use |
|---|---|---|
| 10 % | −3 °C | Not recommended: too weak for inhibitors to work |
| 20 % | −8 °C | Chilled water at +5 °C and above with frost risk |
| 30 % | −15 °C | Fluid leaving at about −5 °C |
| 40 % | −24 °C | Fluid leaving at about −12 °C to −14 °C |
| 50 % | −37 °C | Fluid leaving at about −25 °C |
Propylene glycol freezing point chart
| Propylene glycol (% by volume) | Approximate freezing point | Typical use |
|---|---|---|
| 10 % | −3 °C | Not recommended: too weak and prone to bacterial growth |
| 20 % | −7 °C | Chilled water at +5 °C and above with frost risk |
| 30 % | −13 °C | Fluid leaving at about −3 °C |
| 40 % | −21 °C | Fluid leaving at about −10 °C |
| 50 % | −33 °C | Fluid leaving at about −20 °C; viscosity is high |
Freezing points are approximate published values and vary slightly between suppliers and inhibitor packages. Percent by weight differs a little from percent by volume. Confirm against the data sheet of the product you buy.
How to choose the percentage
The coldest place in the loop is the evaporator tube or plate wall, which sits close to the refrigerant evaporating temperature. That is typically 4 to 6 °C below the leaving fluid temperature. The rule is to keep the freezing point 5 to 8 °C below the evaporating temperature, which works out to about 10 °C below the leaving fluid temperature.
| Leaving fluid temperature | Target freezing point | Ethylene glycol (about) | Propylene glycol (about) |
|---|---|---|---|
| +5 °C (outdoor unit, frost risk) | −5 °C to −8 °C | 20 % | 20 – 25 % |
| 0 °C | −10 °C | 23 – 25 % | 25 – 28 % |
| −5 °C | −15 °C | 30 % | 33 – 35 % |
| −10 °C | −20 °C | 35 – 36 % | 38 – 40 % |
| −15 °C | −25 °C | 40 – 42 % | 43 – 45 % |
| −20 °C | −30 °C | 45 % | 47 – 48 % |
Three limits apply:
- Lower limit. Below roughly 20–25 % the corrosion inhibitors are too dilute to protect the metal, and weak propylene glycol can support bacterial growth. If you need glycol at all, use at least this much.
- Upper limit. More glycol than necessary costs capacity and pump power for no benefit. Above about 60 % the freezing point starts to rise again.
- Winter and standby. An outdoor air cooled chiller on a +7 °C water duty in a cold region needs protection for the lowest night temperature when it is switched off, not only for its operating temperature.
Below about −25 °C glycol becomes thick and other fluids are often a better choice. Calcium chloride, methanol and the working range of each are compared in chilled brine temperature range and brine vs glycol chillers.
Worked example: how much glycol to add
A loop holds 2,000 litres including the tank, and fluid leaves the chiller at −8 °C. Target freezing point is about −18 °C, which the chart puts at roughly 35 % ethylene glycol.
First fill: 2,000 × 0.35 = 700 litres of glycol and 1,300 litres of water.
Correcting a weak loop: after a leak was topped up with water, the refractometer shows 25 %. The volume to drain and replace with concentrated glycol is:
Volume = system volume × (target % − measured %) ÷ (100 − measured %) = 2,000 × (35 − 25) ÷ (100 − 25) = 267 litres.
Check: the 1,733 litres left in the loop contain 433 litres of glycol; adding 267 litres gives 700 litres in 2,000, which is 35 %. Circulate for a few hours and test again.
What glycol costs in capacity and pump power
Glycol carries less heat per litre than water and is more viscous, so the chiller gives slightly less capacity and the pump works harder. Typical corrections for ethylene glycol at chilled-water temperatures are:
| Ethylene glycol | Chiller capacity | Flow for the same duty | Pressure drop at that flow |
|---|---|---|---|
| 20 % | 1 – 2 % lower | 3 – 4 % higher | 10 – 15 % higher |
| 30 % | 2 – 3 % lower | 6 – 9 % higher | 15 – 25 % higher |
| 40 % | 3 – 5 % lower | 10 – 14 % higher | 25 – 35 % higher |
| 50 % | 5 – 7 % lower | 15 – 18 % higher | 35 – 50 % higher |
Typical ranges only. Propylene glycol penalties are larger, and all of them grow as the fluid gets colder. Use the chiller manufacturer's correction factors for selection.
A chiller, pump and heat exchanger selected for water will therefore fall short on glycol. The flow calculation with density and specific heat is shown in chilled water flow rate calculation, and capacity sizing in how to calculate chiller tonnage.
Ethylene or propylene glycol
- Ethylene glycol (MEG) has lower viscosity and better heat transfer, and needs a lower concentration for a given freezing point. It is toxic if swallowed, so it suits closed industrial loops in plastics, chemical and engineering plants.
- Propylene glycol (MPG) has low toxicity. Food, dairy, beverage, brewery and pharmaceutical plants use food-grade inhibited propylene glycol wherever a leak could reach the product. It is more viscous, particularly below about −15 °C, so pumps and heat exchangers must be sized for it.
Do not mix the two in one loop: the concentration can no longer be read reliably. Plant-level choices for food factories are discussed in ammonia vs glycol refrigeration in food plants.
Inhibited glycol only, never automotive antifreeze
Plain glycol slowly oxidises into organic acids that attack steel, copper and solder. Industrial heat-transfer glycols carry an inhibitor package and a pH buffer to prevent this. Automotive antifreeze uses silicate inhibitors that can gel, foul heat exchanger surfaces and shorten pump seal life, so it must not be used in a chiller. Also:
- Dilute with demineralised or soft, low-chloride water. Hard water uses up the inhibitors and leaves scale.
- Avoid galvanised pipe and tanks; zinc reacts with the inhibitors.
- Test pH yearly. Fresh inhibited glycol is usually around pH 8–10. A reading falling towards 7 means the inhibitors are depleted and the fluid needs treatment or replacement.
Checking concentration with a refractometer
- Use a glycol refractometer with separate scales for ethylene and propylene glycol. Check that it reads zero (0 °C freezing point) with clean water.
- Draw a sample from the circulating loop, not from a dead leg, and let it reach room temperature.
- Place a few drops on the prism, close the cover and read the freezing point on the correct scale.
- Record it in the log. Test monthly, and always after a leak, a top-up or work on the pipework.
A hydrometer works reasonably for ethylene glycol but poorly for propylene glycol, whose density is too close to that of water. Diluted glycol is one of the common causes of freeze trips listed in the chiller troubleshooting guide.
Freeze protection and burst protection
Glycol solutions do not freeze solid at one temperature. Ice crystals first appear at the freezing point, and the fluid turns to slush before it becomes solid at a lower temperature. Freeze protection keeps the fluid fully liquid and pumpable. Burst protection uses less glycol and only prevents pipes from splitting while the system stands idle; the fluid may be slush and cannot be circulated. Burst protection is acceptable for a dormant comfort-cooling coil in winter. A running process chiller always needs full freeze protection, because slush blocks the evaporator and lets the tubes freeze.
Teqtive glycol chillers
Teqtive builds glycol chillers and brine chillers from 1 to 500 TR for 0 °C to −40 °C, with evaporators and pumps selected for the actual fluid and concentration, and food and dairy plant chillers on propylene glycol. Tell us your leaving temperature, fluid and load and we will recommend the concentration and the chiller.
Frequently asked questions
What percentage of glycol should be used in a chiller?
Choose the concentration whose freezing point is about 10 °C below the leaving fluid temperature, which keeps it 5 to 8 °C below the evaporating temperature. For fluid leaving at −5 °C that is about 30 % ethylene glycol or 33 to 35 % propylene glycol by volume. Do not go below roughly 20 to 25 %, and avoid more than you need.
What is the freezing point of 30% ethylene glycol?
A 30 % by volume ethylene glycol and water mixture freezes at about −15 °C. For comparison, 20 % freezes at about −8 °C, 40 % at about −24 °C and 50 % at about −37 °C. Values vary by a degree or so between suppliers and inhibitor packages, so confirm with the product data sheet.
Propylene glycol vs ethylene glycol: which is better for a chiller?
Ethylene glycol transfers heat better and is less viscous, so it is the usual choice for industrial process loops. Propylene glycol has low toxicity and is used in food, dairy, beverage and pharmaceutical plants where the coolant could contact product. Propylene glycol needs a slightly higher concentration for the same freezing point and more pump power at low temperatures.
Can I use car antifreeze in an industrial chiller?
No. Automotive antifreeze contains silicate-based inhibitors intended for engine materials and temperatures. In a chiller loop they can gel, coat heat exchanger surfaces, reduce heat transfer and damage pump seals. Use an industrial inhibited ethylene or propylene glycol made for HVAC and process cooling, diluted with good quality water.
How do I check the glycol concentration in my chiller?
Use a glycol refractometer. Put a few drops of fluid at room temperature on the prism and read the freezing point on the scale for your glycol type, since ethylene and propylene glycol have separate scales. Check monthly and after any leak or water top-up. Test pH and inhibitor level at least once a year.