Engineering guide · operation

Chiller Approach Temperature Explained

Approach is the temperature gap between the refrigerant and the water leaving a heat exchanger. Two subtractions on the daily log sheet show fouling, low charge and air in the system before they become a trip.

Teqtive process engineering team · 2026-11-24

Approach temperature in a chiller is the difference between the fluid leaving a heat exchanger and the refrigerant saturation temperature inside it. Evaporator approach = leaving chilled water temperature − evaporating temperature. Condenser approach = condensing temperature − leaving condenser water temperature. On a clean machine both are only a few degrees, and a rising approach at the same load means heat transfer is getting worse.

The definitions

TermFormulaWhat it tells you
Evaporator approachLeaving chilled water (or brine) temperature − saturated evaporating temperatureCondition of the evaporator: fouling, refrigerant charge, oil, refrigerant feed
Condenser approach (water cooled)Saturated condensing temperature − leaving condenser water temperatureCondition of the condenser: scale, non-condensables, charge
Condenser temperature difference (air cooled)Saturated condensing temperature − entering air temperatureCondition of the coil and fans, and air recirculation
Cooling tower approachWater temperature leaving the tower − ambient wet bulb temperatureCondition of the tower, not of the chiller

The saturated temperatures are not measured with a thermometer. They are read from the suction and discharge pressures using the pressure and temperature chart for the refrigerant, and most microprocessor controllers display them directly. Do not confuse approach with the water range, or ΔT, which is entering minus leaving water temperature and depends on load and flow; see chilled water flow rate calculation.

Typical healthy values

Heat exchangerTypical approach when clean, full load
Flooded or falling film shell and tube evaporator (water)1 – 3 °C
Direct expansion shell and tube evaporator (water)3 – 6 °C
Brazed plate evaporator (water)2 – 5 °C
Evaporators on glycol or brine at sub-zero temperatures4 – 8 °C
Water cooled shell and tube condenser1 – 4 °C
Air cooled condenser (condensing − entering air)10 – 15 °C
Cooling tower3 – 5 °C above wet bulb

These are typical ranges. Design values differ between manufacturers and models, so the reference for your chiller is its own data sheet and the readings recorded at commissioning.

Approach changes with load. At half load a heat exchanger transfers half the heat through the same surface, so the approach is roughly half the full-load value. Always compare readings taken at similar load, or note the load beside every reading.

Why approach matters

The compressor does not see water temperatures. It sees the evaporating and condensing pressures, and the gap between them is the lift it has to work against. Every degree added to either approach widens that lift. As a rule of thumb each 1 °C of extra lift costs roughly 2–3 % more compressor power, and capacity falls at the same time. Approach is therefore both a maintenance indicator and an energy indicator; see chiller power consumption calculation.

Worked example

A water cooled screw chiller is logged at full load on two dates, with the same chilled water set point and the same condenser water temperatures.

ReadingAt commissioningEight months later
Leaving chilled water7.0 °C7.0 °C
Saturated evaporating temperature4.5 °C2.0 °C
Evaporator approach2.5 °C5.0 °C
Leaving condenser water35.0 °C35.0 °C
Saturated condensing temperature37.5 °C41.0 °C
Condenser approach2.5 °C6.0 °C
Compressor lift (condensing − evaporating)33.0 °C39.0 °C

The evaporator approach has risen by 2.5 °C and the condenser approach by 3.5 °C, so the compressor now works against 6 °C more lift. At 2–3 % per degree that is roughly 12–18 % more compressor power for the same cooling. On a compressor that drew 70 kW when clean, the penalty is about 8 to 13 kW, every running hour, and the water temperatures alone would never have shown it.

What a rising approach means

Evaporator approach rising

  • Fouled or scaled tubes on the water or brine side. Open circuits and dirty process water are the usual reason.
  • Low refrigerant charge. Part of the surface is starved. Look for high suction superheat and bubbles in the liquid line sight glass.
  • Oil logged in the evaporator, coating the refrigerant side. Check the oil level and the oil return system.
  • Expansion valve underfeeding or a blocked filter drier, which behaves like low charge.
  • Low water flow. The ΔT across the evaporator rises and the evaporating temperature drops. Check strainers, valves and the pump.
  • Glycol stronger or colder than design, which raises viscosity and lowers heat transfer. See the glycol concentration chart.

Condenser approach rising

  • Scale, slime or mud in the tubes. By far the most common cause on cooling tower water.
  • Non-condensable gas, usually air admitted during service. Head pressure is high even with clean tubes and normal water flow.
  • Refrigerant overcharge. Liquid backs up and covers tubes; subcooling is unusually high.
  • Blocked tubes or a leaking division plate in the water box, which lets water bypass part of the tube bundle.
  • On air cooled chillers: dirty or damaged fins, a failed fan, or hot discharge air drawn back into the coil.
Symptom patternMost likely causeFirst check
Condenser approach high, water ΔT normal, subcooling normalFouled condenser tubesInspect and brush tubes; review water treatment
Condenser approach high soon after service workNon-condensablesCompare standstill pressure with saturation pressure at ambient
Condenser approach high, subcooling highOverchargeRecover refrigerant to the nameplate charge
Condenser water ΔT high, head pressure highLow condenser water flowStrainer, pump, valves, tower basin level
Evaporator approach high, superheat highLow charge or underfeeding valveLeak test; check drier and expansion valve
Evaporator approach high, superheat normalFouled evaporator or oil loggingWater quality, oil level, tube inspection

Step-by-step fault finding for each of these is in the industrial chiller troubleshooting guide.

How to log and trend approach

  1. Set a baseline. Record both approaches at commissioning, or just after the tubes have been cleaned, at or near full load.
  2. Log daily at a steady condition. Note leaving chilled water, evaporating temperature, leaving and entering condenser water, condensing temperature, load or compressor current, and ambient.
  3. Calculate the two approaches and add them as columns on the log sheet or in the building management system.
  4. Plot them weekly against the baseline, comparing only readings at similar load.
  5. Set action levels. A common practice is to investigate when either approach is 1.5–2 °C above baseline and to clean or repair at 2–3 °C above.
  6. Check the instruments. A sensor error of 0.5 °C is a large part of a 2 °C approach, so verify temperature sensors and pressure transducers before opening the machine.

Trending turns tube cleaning from a calendar job into a condition-based one. The full routine is in the industrial chiller maintenance checklist, and the efficiency background in chiller efficiency, COP and kW/TR.

Teqtive chillers and service

Teqtive water cooled screw chillers, air cooled screw chillers and brine chillers are supplied with the design evaporating and condensing temperatures on the data sheet, which gives you the baseline approach from day one. For help reading your log sheet or planning a condenser clean, contact our service team.

Frequently asked questions

What is approach temperature in a chiller?

Approach is the difference between the temperature of the fluid leaving a heat exchanger and the saturation temperature of the refrigerant inside it. Evaporator approach is leaving chilled water temperature minus evaporating temperature. Condenser approach is condensing temperature minus leaving condenser water temperature. A small, steady approach means the heat exchanger is clean and working properly.

What is a good evaporator approach temperature?

Typical full-load values on a clean machine are about 1 to 3 °C for flooded and falling film evaporators, 3 to 6 °C for direct expansion shell and tube evaporators and 2 to 5 °C for brazed plate evaporators. Brine and glycol duty runs higher. The best reference is the value recorded at commissioning on your own chiller.

What is a normal condenser approach temperature?

For a clean water cooled shell and tube condenser at full load, condenser approach is typically 1 to 4 °C. For an air cooled condenser the equivalent figure, condensing temperature minus entering air temperature, is typically 10 to 15 °C. A rise of 2 to 3 °C above the clean baseline at the same load usually means the condenser needs cleaning.

What causes high condenser approach temperature?

The usual cause is scale, slime or mud on the water side of the condenser tubes. Other causes are air or other non-condensable gas in the condenser, refrigerant overcharge backing liquid up over the tubes, and blocked tubes or division plate leakage. On air cooled chillers, dirty coils, failed fans and hot air recirculation have the same effect.

How do you calculate chiller approach?

Read the saturated evaporating and condensing temperatures from the controller, or convert suction and discharge pressures using the pressure and temperature chart for your refrigerant. Then subtract: evaporator approach = leaving chilled water temperature − evaporating temperature; condenser approach = condensing temperature − leaving condenser water temperature. Compare readings taken at similar load.