Troubleshooting guide

Chiller High Pressure and Low Pressure Trips: Causes, Checks and Fixes

High pressure and low pressure trips account for most chiller stoppages. Each has a short list of causes, and a few readings taken in the right order will separate them without guesswork.

Teqtive process engineering team · 2026-11-24

A chiller trips on high pressure (HP) when the condenser cannot get rid of heat, and on low pressure (LP) when the evaporator is short of either refrigerant or heat. Dirty condensers and poor airflow or water flow cause most HP trips. Refrigerant leaks, low chilled water flow and blocked filter driers cause most LP trips. The steps below narrow it down from a handful of readings.

Safety first. Never bypass, bridge or re-set the value of an HP switch, LP switch, flow switch or antifreeze thermostat to keep a chiller running. Work on the refrigerant circuit, including charging, recovery, purging and valve adjustment, must be done by qualified refrigeration technicians. Isolate power before working on fans, pumps or panels.

For a wider chart covering oil, flow, overload and other alarms, see the industrial chiller troubleshooting guide. This article goes deeper into the two pressure trips.

What the two switches are telling you

At a given pressure a refrigerant condenses or evaporates at one temperature, so a pressure gauge is really a thermometer for the inside of the heat exchanger. Convert the reading to saturation temperature with the gauge scale or a chart for your refrigerant, then compare it with the air or water temperature outside the tubes.

ReadingHealthy value (typical)What a larger gap means
Condensing temperature minus ambient air (air cooled)10–15 °CCoil dirty, airflow short, overcharge or air in system
Condensing temperature minus leaving condenser water (water cooled)About 5–8 °C or lessTubes scaled or fouled, overcharge or air in system
Leaving chilled fluid minus evaporating temperatureAbout 3–8 °C depending on evaporator typeEvaporator starved of refrigerant, short of flow or fouled
Superheat at evaporator outletAbout 5–8 °CHigh: starved evaporator. Low: overfeeding or low heat load
Subcooling at condenser outletAbout 3–8 °CHigh: overcharge. Low: undercharge

These are typical ranges. Your commissioning record is the real reference.

High pressure trip: air cooled chillers

  • Dirty condenser coil. Dust, lint and oil mist block the fins. This is the commonest cause.
  • Fan failure. A tripped motor, loose blade, reversed rotation after electrical work, or a faulty fan controller.
  • High ambient. A unit selected for 35–40 °C will run out of margin at 45 °C.
  • Hot air recirculation. Walls, sheds or neighbouring units closer than the stated clearance send discharge air back into the coil.
  • Refrigerant overcharge. Liquid backs up in the condenser and covers tubes that should be condensing. Subcooling is high.
  • Non-condensable gas. Air or nitrogen left after service occupies condenser space and adds its own pressure.

High pressure trip: water cooled chillers

  • Scaled or fouled condenser tubes. The approach between condensing temperature and leaving water rises steadily over weeks.
  • Low cooling tower water flow. A choked strainer, a partly closed valve, a worn pump or a low basin level. The water temperature rise across the condenser is higher than design.
  • High tower water temperature. Tower fan off, clogged fill, blocked nozzles, or an undersized tower. See cooling tower vs chiller for what a tower can and cannot do.
  • Overcharge and non-condensables, as above.

HP trip: checks in order

  1. Note ambient or entering condenser water temperature at the time of the trip.
  2. Air cooled: confirm every fan runs in the correct direction. Shine a torch through the coil; if light does not pass the fins, wash it.
  3. Air cooled: measure air temperature entering the coil. If it is several degrees above ambient in the open, recirculation is the fault.
  4. Water cooled: read condenser water in and out. A rise larger than design means low flow. A normal rise with hot inlet water points to the tower.
  5. Clean the strainer and confirm valve positions and pump current.
  6. If the gap between condensing and water temperature is still high with good flow, the tubes need descaling.
  7. If the condenser is clean and flow is correct, call a technician to check for overcharge and non-condensables.

Worked example

An air cooled R-134a chiller trips on HP on a 40 °C afternoon. Just before the trip the discharge gauge read 17.9 bar g, which is 18.9 bar absolute. For R-134a that corresponds to a condensing temperature of about 65 °C. The gap to ambient is 65 − 40 = 25 °C against a healthy 10–15 °C. At a normal 53 °C condensing the gauge would show about 13.2 bar g. The condenser is transferring heat poorly, so start with the coil and fans, not with the refrigerant charge. Other refrigerants have different pressures, so use the correct chart.

Low pressure trip: causes

  • Low refrigerant charge. Always the result of a leak.
  • Low chilled water or glycol flow. Blocked strainer, failed or reversed pump, closed valve or air in the loop. The temperature drop across the evaporator is larger than design.
  • Blocked filter drier. A measurable temperature drop across the drier, sometimes with frost at its outlet.
  • Expansion valve fault. Loose bulb, lost bulb charge, blocked inlet strainer, moisture freezing in the orifice, or a failed electronic valve or sensor.
  • Low load. Return water near set point with the compressor at minimum capacity; common on oversized chillers and in winter.
  • Weak glycol or brine. Ice forms on the tubes, insulates them and pulls suction pressure down further. This can split the evaporator.

LP trip: checks in order

  1. Confirm the chilled water pump is running, the strainer is clean and all valves are open. Compare evaporator inlet and outlet temperatures with design.
  2. Check the set point has not been lowered below the value the chiller and coolant were designed for.
  3. On glycol or brine systems, test concentration with a refractometer. The freezing point should be roughly 5–10 °C below the lowest evaporating temperature. See chilled brine temperature range.
  4. Look at the liquid sight glass at steady load. Continuous bubbles suggest low charge or a restriction upstream.
  5. Feel for a temperature drop across the filter drier.
  6. Have a technician measure superheat and subcooling. High superheat with low subcooling indicates low charge. High superheat with normal or high subcooling indicates a restriction: the drier or the expansion valve. Low superheat with low suction indicates low flow, low load or a fouled evaporator.

Cause, symptom and fix

TripCauseTell-tale symptomFix
HPDirty air cooled coilHigh condensing-to-ambient gap; worse in the afternoonWash fins from inside out with low-pressure water; set a cleaning interval
HPFan not running or reversedLow airflow over part of the coilRepair motor or controller; correct rotation
HPAir recirculationAir entering coil hotter than open ambientRestore clearances; remove obstructions; duct discharge away
HPScaled condenser tubesApproach to leaving water rising over weeksDescale tubes; correct water treatment
HPLow tower flow or choked strainerLarge water temperature rise across condenserClean strainer; check pump, valves and basin level
HPHot tower waterInlet water well above wet bulb plus 5 °CService tower fan, fill and nozzles
HPOvercharge or non-condensablesHigh head pressure with a clean condenser and correct flowTechnician to correct charge, or evacuate and recharge
LPRefrigerant leakBubbles in sight glass; high superheat; low subcoolingLeak test, repair, evacuate, recharge by weight
LPLow chilled fluid flowLarge temperature drop across evaporatorClean strainer; vent air; check pump and valves
LPBlocked filter drierTemperature drop or frost across drierTechnician to replace drier core
LPExpansion valve faultHunting or very high superheat with full sight glassCheck bulb, strainer, sensor; adjust or replace
LPLow loadTrips at night or in winter; short cyclingAdd buffer volume; widen differential
LPWeak glycolSuction falls steadily; flow drops as ice formsStop, thaw, correct concentration before restart

Preventing repeat trips

Most of these faults build up slowly and show in the daily log long before the switch opens. Record pressures, fluid temperatures and ambient every shift, and act when the approach temperatures drift. A cleaning and inspection schedule is given in the industrial chiller maintenance checklist. Many trips on new plants trace back to installation faults such as short clearances or missing strainers, which are covered in the chiller installation and commissioning checklist.

Teqtive service and chillers

Teqtive selects its air cooled scroll and air cooled screw chillers for Indian summer ambients, and builds water cooled and glycol chillers for process duty. If your chiller keeps tripping, send the alarm, the pressure and temperature readings and the refrigerant type through the contact page and our service engineers will help you identify the cause.

Frequently asked questions

What causes a high pressure alarm on a chiller?

A high pressure alarm means the condenser cannot reject heat fast enough. On air cooled chillers the usual causes are a dirty coil, a failed fan, very high ambient or hot air recirculating into the coil. On water cooled chillers they are scaled tubes, low cooling tower flow, a choked strainer or hot tower water. Refrigerant overcharge and air in the circuit also raise head pressure.

Why does my chiller trip on low pressure?

A low pressure trip means the evaporator pressure has fallen below the safe limit. Either too little refrigerant is reaching the evaporator, because of a leak, a blocked filter drier or a faulty expansion valve, or too little heat is reaching it, because of low water flow, a very low load or glycol that has begun to freeze on the tubes.

Why does my chiller trip on high pressure only in summer afternoons?

Head pressure rises with ambient temperature. A condenser that is partly dirty or short of airflow copes at 30 °C but reaches the trip setting at 42–45 °C. Clean the coil, check all fans, remove obstructions and make sure hot discharge air is not being drawn back in. On water cooled units check tower performance at peak wet bulb.

Can I bypass or raise the HP or LP switch setting to keep the chiller running?

No. The high pressure switch protects against rupture of the pressure vessel and piping, and the low pressure switch protects the evaporator from freezing and the compressor from overheating. Bypassing or raising settings beyond the manufacturer's values risks injury, a burst evaporator or a burnt compressor. Find and fix the cause instead.

How do I know if my chiller is low on refrigerant?

Typical signs are low suction pressure, high superheat at the evaporator outlet, low subcooling at the condenser outlet and bubbles in the liquid line sight glass at steady full load. The chiller struggles to reach set point. Low charge always means a leak, so a technician must find and repair it before adding refrigerant.