Chiller Capacity Control Methods: Staging, Slide Valve, VFD and Hot Gas Bypass

A process chiller spends most of its life below full load. How it reduces capacity decides its part-load power bill, how steadily it holds temperature and how long the compressor lasts.

Teqtive process engineering team · 2026-11-24

Chiller capacity control is how the machine matches its cooling output to a load that is smaller than its rating. The main methods are compressor staging, cylinder unloading on reciprocating compressors, slide valve control on screw compressors, digital or inverter scroll compressors, variable frequency drives (VFD) and hot gas bypass. Speed control and staging keep efficiency high at part load, a slide valve loses some, and hot gas bypass wastes the most.

Why part load matters

A chiller is sized for the worst hour: peak production on the hottest day. For most of the year the load is lower, the ambient is cooler, or both. Ratings such as IPLV weight the 50 % and 75 % load points far more heavily than 100 %; see IPLV and NPLV explained. A chiller that is efficient at full load but poor at 50 % can cost more to run than its nameplate kW/TR suggests.

The methods

On/off cycling

The simplest control: the compressor runs at full capacity until the water reaches set point, then stops. Each start stresses the motor and returns oil poorly, so makers limit starts per hour (typically 6–12; check the compressor data). The loop needs enough water volume, often a buffer tank, to keep the off period long enough.

Multi-compressor staging

Several compressors share the duty and a controller switches them in and out. Four equal scrolls give 25, 50, 75 and 100 %. Each running compressor works at its full-load efficiency, and with fewer compressors on the same condenser and evaporator the temperature approaches shrink, so kW/TR at part load is often better than at full load. Independent circuits also give redundancy. This is the normal arrangement on scroll chillers.

Cylinder unloading (reciprocating)

A solenoid holds the suction valves of selected cylinders open, or blocks their suction, so those cylinders pump no gas. A four-cylinder machine gives 50 and 100 %; six cylinders give 33, 67 and 100 %; eight give 25, 50, 75 and 100 %. Power falls nearly in proportion, but the unloaded pistons still add friction.

Slide valve (screw)

A sliding valve under the rotors returns part of the suction gas before it is compressed, shortening the working length of the rotors. Control is in steps or stepless from about 25 % to 100 %. Efficiency holds up well down to about 75 % and then falls away: at minimum position a screw may still draw roughly 40–50 % of full-load power for 25 % capacity (typical; check the compressor data). See screw chillers.

Digital scroll

The two scrolls are separated axially for part of a short repeating cycle, typically 10–20 seconds. While separated the compressor pumps nothing and draws little power. Varying the loaded fraction gives about 10–100 % capacity without a drive.

Inverter scroll and VFD screw

A variable frequency drive changes motor speed, and displacement follows speed. The compressor pumps less gas instead of compressing gas and then discarding it, so this is the most efficient way to turn down. Minimum speed is limited by oil circulation and motor cooling, typically about 25–30 % of rated speed. The drive adds about 2–4 % loss at full load and must be matched to a compressor approved for variable speed.

Hot gas bypass

A regulating valve feeds discharge gas to the evaporator inlet or the suction line when suction pressure falls. The evaporator sees an artificial load, so the compressor keeps running at very low real load without freezing the evaporator or cycling. The compressor's power hardly changes, which is why this method is so wasteful. It is justified for short periods, for very tight temperature control, or as the last step below a compressor's minimum unloading.

Comparison table

Typical ranges for guidance; actual values depend on the compressor model and operating conditions.

MethodCompressor typeTypical turndownEffect on part-load efficiency
On/off cyclingAny single compressor0 or 100 %Fair; cycling losses and temperature swing
Multi-compressor stagingScroll, reciprocating, screwSteps of 100 ÷ N % (4 compressors: 25 %)Good; often better kW/TR than full load
Cylinder unloadingReciprocating100 / 67 / 33 % or 100 / 75 / 50 / 25 %Fair to good; friction of idle cylinders remains
Slide valveScrewStepped or stepless, about 25–100 %Good above 75 %, falling below 50 %
Digital scrollScrollAbout 10–100 %Moderate; some power drawn while unloaded
VFD / inverterScroll, screw, centrifugalAbout 25–100 % of speedBest; power falls close to capacity
Hot gas bypassAnyDown to about 0–10 % loadPoor; power stays near the full value

Worked example: 12 TR load on a 30 TR compressor

A fixed-speed 30 TR compressor draws 24 kW at full load, which is 0.80 kW/TR. The process needs only 12 TR (40 %) for 4,000 hours a year. The figures below are illustrative and exclude pumps and fans.

Control methodCompressor power at 12 TRkW/TREnergy over 4,000 h
Hot gas bypass, compressor runs continuously24 kW24 ÷ 12 = 2.0024 × 4,000 = 96,000 kWh
On/off cycling with buffer tank, 40 % run time0.40 × 24 = 9.6 kW average0.80, plus cycling losses9.6 × 4,000 = 38,400 kWh
VFD at an assumed 0.75 kW/TR12 × 0.75 = 9.0 kW0.759.0 × 4,000 = 36,000 kWh

Hot gas bypass uses 96,000 − 36,000 = 60,000 kWh a year more than speed control for the same cooling, and 2.00 ÷ 0.80 = 2.5 times the energy per TR of the same compressor at full load. Cycling with a buffer tank comes close to the VFD on energy but with a wider temperature band and more starts. The kW/TR arithmetic is in chiller efficiency, COP and kW/TR.

Choosing a method for your load

Load profileSuitable approach
Steady load near full capacity all yearFixed-speed compressor, staged if more than one
Load varies in broad steps, such as machines switched on and offMulti-compressor staging
Continuously varying load on a large plantStepless slide valve or VFD screw
Small chiller needing tight temperature control, about ±0.5 °CDigital or inverter scroll; hot gas bypass only for the last step
Occasional very low loadBuffer tank sized for the minimum stage

Practical points

  • Do not oversize. An oversized chiller spends its life at the inefficient end of its control range. Size from a real load calculation, not from the largest machine on the floor.
  • At low load the refrigerant velocity falls and oil may not return. Follow the maker's minimum load and run-time limits.
  • Check superheat at minimum load as well as full load; expansion valves hunt most when unloaded.

Teqtive chillers

Teqtive builds air cooled scroll chillers from 5 to 78 TR, air cooled and water cooled screw chillers from 40 to 500 TR, and reciprocating chillers from 1 to 120 TR. Share your peak load, minimum load and the hours spent at each, and we will propose a compressor arrangement and control method that suits the profile.

Frequently asked questions

What is capacity control in a chiller?

Capacity control is the way a chiller matches its cooling output to the actual load. Methods include switching compressors on and off, unloading cylinders on reciprocating compressors, moving the slide valve on a screw compressor, modulating a digital scroll, changing compressor speed with a VFD, and hot gas bypass. Each has a different turndown and part-load efficiency.

How does a slide valve work in a screw compressor?

The slide valve is a sliding section of the compressor housing beneath the rotors. Moving it opens a path that returns part of the trapped gas to suction before compression starts, which shortens the effective rotor length. Capacity falls in steps of 25, 50, 75 and 100 %, or steplessly from about 25 % to 100 %.

Is a VFD chiller more efficient?

At part load, usually yes. A variable frequency drive slows the compressor so it pumps less gas, and power falls almost in step with capacity. At full load the drive itself loses about 2–4 %, so a VFD pays where the chiller runs many hours between roughly 30 % and 80 % load, and adds little if the load is steady near 100 %.

Why is hot gas bypass inefficient?

Hot gas bypass does not reduce the compressor's work. It diverts discharge gas back to the low-pressure side to create a false load, so the compressor keeps drawing close to full power while the useful cooling falls. A 30 TR compressor carrying a 12 TR load on hot gas bypass uses about 2.5 times the energy per TR.

What is the minimum load a chiller can run at?

It depends on the control method. A single on/off compressor has no stable minimum and cycles. A four-compressor scroll chiller steps down to 25 %. Screw compressors with a slide valve typically reach 25 %, digital scrolls about 10 %, and VFD compressors about 25–30 % of rated speed. Below the minimum the chiller cycles or needs a buffer tank.